Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and continuous duty applications. All generator sets are factory build, and production tested.
| MODEL | APD13A | ||
| Power Pf. 0.8 | Standby | kVA | 12 |
| kW | 9.6 | ||
| Prime | kVA | 11 | |
| kW | 8.8 | ||
Standby : Continuous running at variable load for duration of an emergency. No overload is permitted on these ratings. In accordance with ISO 3046 .
Prime : Continuous running at variable load for unlimited periods with 10% overload available for 1 hour in any 12 hour period. In accordance with ISO 8528,ISO 3046.
✓ High quality, reliable and complete power unit
✓ Compact design
✓ Easy start and maintenance possibility
✓ Every generating set is subject to a comprehensive test program which includes full load testing, checking and provision of all control and safety shut down functions testing
✓ Fully engineered with a wide range of options and accessories: Canopy, sound proof canopy and on-road trailer
| MODEL | APD13A | ||
| Power Pf. 0.8 | Standby | kVA | 12 |
| kW | 9.6 | ||
| Prime | kVA | 11 | |
| kW | 8.8 | ||
| MODEL | A3CRX14 | |
| Rngine power output at rated rpm | kWM | 14 |
| HP | 18.76 | |
| Aspiration and cooling | natural | |
| Total displacement | Litre | 1.357 |
| No. of cylinders and build | 3- inline | |
| Engine speed | RPM | 1500 |
| Bore and stroke | mmxmm | 80x90 |
| Compression ratio | 18:1 | |
| Governor | Mechanical | |
| Fuel consumption at full load | L/Hr | 3.7 |
| Fuel tank capacity | Litre | Open: 32/Canopy: 32 |
| Oil capacity | Litre | 6.5 |
| Coolant capacity | Litre | 18.5 |
| Radiator cooling air | M³/min | 192 |
| Air intake – engine | M³/min | 0.93 |
| Exhaust gas flow | M³/min | 4.5 |
✓ Heavy duty Aksa diesel engine ✓ Cooling radiator and fan
✓ Four stroke, Forced water cooling, Natural ✓ Starter battery (with lead acid) including Rack and Cables
✓ Direct injection fuel system ✓ Flexible fuel connection hoses and manual oil sump drain valve
✓ Mechanical Governor system ✓ Industrial capacity exhaust silencer and steel bellows
✓ 12/24 V D.C. starter and charge alternator ✓ Jacket water heater(at automatic models)
✓ Replaceable fuel filter, oil filter and dry element air filter ✓ Operation manuals and circuit diagram documents
| Design | Brushless single bearing, revolving field |
| Stator | 2/3 pitch |
| Rotor | Single bearing, flexible disc |
| Insulation system | Class h |
| Standard temperature rise | 125 - 163°c continuous |
| Exciter type | Self excited |
| Phase rotation | a (u), b (v), c (w) |
| Alternator cooling | Direct drive centrifugal blower fan |
| Ac waveform total harmonic distortion | No load < 1.5%. non distorting balanced linear load < 5% |
| Telephone influence factor (tif) | <50 per nema mg1-22.43 |
| Telephone harmonic factor (thf) | <2% |
|
Open type |
||
| Dimensions (lxwxh) | mm | 1400*760*927 |
| Dry weight | kg | 350 |
|
Sound attenuated type |
||
| Dimensions (lxwxh) | mm | 1522*823*1127 |
| Dry weight | kg | 470 |
Accessories
✓ Bulk fuel tank
✓ Automatic filling system
✓ Fuel-water separator filter
✓ Low fuel level alarm
✓ Residential silencer
✓ Enclosure or sound proof canopy
✓ Trailer
✓ Manual oil drain pump
✓ Tool kit for maintenance